Title:
|
Harmonic resonance stability of aeronautical ground lighting systems
|
Author:
|
Vidal, Daniel; Monjo Mur, Lluís; Sainz Sapera, Luis
|
Other authors:
|
Universitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica; Universitat Politècnica de Catalunya. QSE - Qualitat del Subministrament Elèctric |
Abstract:
|
© 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works. |
Abstract:
|
Aeronautical ground lighting (AGL) systems assist aircraft pilots in airport operations. These systems are singlephase series circuits where constant current regulators (CCRs) feed luminaires with an adjustable rms current. CCRs are voltage source converters (VSCs) which may cause harmonic resonance instabilities when their control interacts with poorly damped resonances in the 0.75 - 2.5 kHz range. The paper studies these instabilities from the impedance-based representation of AGL systems which are grid-connected VSC systems much simpler than the usual systems analyzed in the literature. This offers the possibility of contributing with a comprehensive stability assessment. Approximate expressions of the CCR and AGL circuit equivalent admittances are given to assess system stability. A comprehensive overview of the influence of AGL system parameters on harmonic resonance instabilities is presented and several recommendations on the AGL system components and CCR parameters are proposed to improve stability. Additionally, an active damping solution based on virtual conductances is analyzed. The expressions of the CCR admittance and some of the recommendations on CCR and AGL system parameters contribute to stability studies of grid-connected VSC systems. Matlab/Simulink and PSCAD/EMTDC simulations of a 68 luminaire AGL system illustrate the contributions of this paper. Field measurements support the stability study. |
Subject(s):
|
-Àrees temàtiques de la UPC::Aeronàutica i espai::Aeroports -Àrees temàtiques de la UPC::Enginyeria electrònica -Àrees temàtiques de la UPC::Enginyeria electrònica::Circuits electrònics -Airports -Harmonic analysis -Luminotecnia -Electronic circuits -AGL systems -Harmonic resonance stability -Impedance modeling -Voltage source converters -Eenergy saving policies -Aeroports -Anàlisi harmònica -Luminotècnia -Circuits electrònics |
Rights:
|
Attribution-NonCommercial-NoDerivs 3.0 Spain
http://creativecommons.org/licenses/by-nc-nd/3.0/es/ |
Document type:
|
Article - Submitted version Article |
Published by:
|
Institute of Electrical and Electronics Engineers (IEEE)
|
Share:
|
|