<?xml version="1.0" encoding="UTF-8"?><?xml-stylesheet type="text/xsl" href="static/style.xsl"?><OAI-PMH xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/ http://www.openarchives.org/OAI/2.0/OAI-PMH.xsd"><responseDate>2026-04-14T02:10:06Z</responseDate><request verb="GetRecord" identifier="oai:www.recercat.cat:10459.1/47747" metadataPrefix="qdc">https://recercat.cat/oai/request</request><GetRecord><record><header><identifier>oai:recercat.cat:10459.1/47747</identifier><datestamp>2024-12-05T22:22:39Z</datestamp><setSpec>com_2072_3622</setSpec><setSpec>col_2072_479130</setSpec></header><metadata><qdc:qualifieddc xmlns:qdc="http://dspace.org/qualifieddc/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:dcterms="http://purl.org/dc/terms/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns:doc="http://www.lyncode.com/xoai" xsi:schemaLocation="http://purl.org/dc/elements/1.1/ http://dublincore.org/schemas/xmls/qdc/2006/01/06/dc.xsd http://purl.org/dc/terms/ http://dublincore.org/schemas/xmls/qdc/2006/01/06/dcterms.xsd http://dspace.org/qualifieddc/ http://www.ukoln.ac.uk/metadata/dcmi/xmlschema/qualifieddc.xsd">
   <dc:title>Free-cooling of buildings with phase change materials</dc:title>
   <dc:title>Refroidissement natruel d’immeubles a` l’aide de mate´riaux changement de phase</dc:title>
   <dc:creator>Zalba, Belén</dc:creator>
   <dc:creator>Marín, José M.</dc:creator>
   <dc:creator>Cabeza, Luisa F.</dc:creator>
   <dc:creator>Mehling, Harald</dc:creator>
   <dc:subject>Air conditioning</dc:subject>
   <dc:subject>Residential building</dc:subject>
   <dc:subject>Modelling</dc:subject>
   <dcterms:abstract>In this paper, the application of phase change materials (PCM) in free-cooling systems is studied. Free-cooling is understood&#xd;
as a means to store outdoors coolness during the night, to supply indoors cooling during the day. The use of PCMs is suitable&#xd;
because of the small temperature difference between day indoors and night outdoors. An installation that allows testing the&#xd;
performance of PCMs in such systems was designed and constructed. The main influence parameters like ratio of&#xd;
energy/volume in the encapsulates, load/unload rate of the storage, and cost of the installation were determined, and&#xd;
experiments were performed following the design of experiments strategy. The statistical analysis showed that the effects with&#xd;
significant influence in the solidification process are the thickness of the encapsulation, the inlet temperature of the air, the air&#xd;
flow, and the interaction thickness X temperature. For the melting process the same holds, but the inlet air temperature had a&#xd;
higher influence than the thickness of the encapsulation. With the empirical model developed in this work, a real free-cooling&#xd;
system was designed and economically evaluated.</dcterms:abstract>
   <dcterms:dateAccepted>2024-12-05T22:22:39Z</dcterms:dateAccepted>
   <dcterms:available>2024-12-05T22:22:39Z</dcterms:available>
   <dcterms:created>2024-12-05T22:22:39Z</dcterms:created>
   <dcterms:issued>2015-01-28T09:29:39Z</dcterms:issued>
   <dcterms:issued>2025-01-01</dcterms:issued>
   <dcterms:issued>2004</dcterms:issued>
   <dc:type>article</dc:type>
   <dc:type>publishedVersion</dc:type>
   <dc:identifier>http://hdl.handle.net/10459.1/47747</dc:identifier>
   <dc:relation>Reproducció del document publicat a https://doi.org/10.1016/j.ijrefrig.2004.03.015</dc:relation>
   <dc:relation>International Journal of Refrigeration, 2004, núm. 27, p. 839–849</dc:relation>
   <dc:rights>(c) Elsevier, 2004</dc:rights>
   <dc:rights>info:eu-repo/semantics/restrictedAccess</dc:rights>
   <dc:publisher>Elsevier</dc:publisher>
</qdc:qualifieddc></metadata></record></GetRecord></OAI-PMH>