DC-link voltage oscilations reduction during unbalanced grid faults for high power wind turbines
Miranda, Hernan; Teodorescu, Remus; Rodríguez Cortés, Pedro; Helle, L.
Universitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica; Universitat Politècnica de Catalunya. SEER - Sistemes Elèctrics d'Energia Renovable
During unbalanced grid voltage faults the Power injected to the grid experiences 100Hz oscillations as a result of interactions between positive and negative sequence components of three-phase voltages and currents. These oscillations can become as high as %50 percent of the rated power. In this article an improved controller is proposed which present different behavior during normal operation and faults to keep track of non-sinusoidal current reference signals. The reference signals are calculated to obtain zero power oscillations. Reconfigurable resonant controllers are used for this purpose applied to 3-level Neutral-point-clamped converter in the megawatt range.
Peer Reviewed
-Àrees temàtiques de la UPC::Energies::Energia elèctrica::Automatització i control de l'energia elèctrica
-Àrees temàtiques de la UPC::Energies::Energia eòlica::Aerogeneradors
-Electric power system stability
-Wind turbines
-Xarxes elèctriques -- Estabilitat
-Aerogeneradors
Article - Published version
Conference Object
         

Show full item record

Related documents

Other documents of the same author

Sintamarean, Craiun; Cantarellas, A.; Miranda, Hernan; Rodríguez Cortés, Pedro; Teodorescu, Remus
Miranda, Hernan; Teodorescu, Remus; Rodríguez Cortés, Pedro; Helle, Lars
Senturk, Osman S.; Munk-Nielsen, Stig; Teodorescu, Remus; Helle, L.; Rodríguez Cortés, Pedro
Altin, M.; Goksu, O.; Teodorescu, Remus; Rodríguez Cortés, Pedro; Bak-Jensen, Birgitte; Helle, L.
 

Coordination

 

Supporters